| Capacity | Powerstab™ 3KVA to 200KVA 3PH-3PH IGBT based PWM output Isolation Transformer |
| INPUT |
| Input Voltage | 415VAC + 15%-25% in 3 Phase 4 Wire 3PH 50Hz +3Hz |
| Frequency | 50Hz + 3Hz |
| Power Factor | >0.9 Typical |
| OUTPUT |
| Nominal Output Voltage | 220V/230V/240 V ± 1% AC |
| Full load Current | Rated at 0.8 PF |
| Nominal Frequency | 50 Hz ± 1 % |
| Power Factor | 0.8 PF |
| Output Wave Form | Sinusoidal |
| Over Load at 0.8 P.F | 125 % for 10 Minutes , 150% for 1 Minute |
| Static Voltage Regulation |
+1% of nominal for all variations of line load
|
| Dynamic voltage Regulation | +6% for 50% Step load Change + 10% for 10% to 100% step load change |
| Total Harmonic Distortion (THD) | For Linear loads <3%, Non Linear loads <5% |
| Crest Factor | 3:1 |
| Inverter Efficiency | 85% to 93% on full load depending on capacity |
| Battery/Charger |
| Battery Type | SMF/ TUBULAR |
| Nominal Float Voltage | 360 V DC |
| Charger Type (6 pulse Rectifier) | Constant Voltage, Constant Current |
| Recharge Time | 8-10 Hours for 100 % Recovery |
| By PassFaclity | Manual by pass |
| PROTECTIONS |
| Charger | Input Circuit Breaker , Charger Over Voltage, Charger Over Current Limit, Phase Sequence / Phase Failure, Abnormal |
| Battery | Battery Low Cutoff, Current Limit, MCB Protection, Battery Over Charge Trip |
| Inverter | O/P OV, UV Trip, Current Limit, Short Circuit Protection |
| MONITORING & DISPLAY FUNCTIONS |
| Indications | Mains On , Inverter On, Battery Low, Trip |
| Display | I/P Voltage , O/P Voltage O/P Load Current, DC Voltage,O/P Frequency |
| Switches | Inverter ON/OFF, Reset & Menu Select |
| ENVIRONOMENTAL |
| Operating Temperature | 0 to 40 °C/ 32 to 104 °F |
| Humidity | 95 %RH Maximum, Non Condensing |
| Max. operating Altitude | 7500Ft, 2285M |
| Acoustic Noise | <60 db |