| Type | Online (True Double Conversion) |
| Capacity | 2 KVA to 10 KVA, Single Phase |
| Input Frequency | 50 Hz ± 5% |
| Input Voltage | 160V – 270V |
| Output Voltage | 230V ± 1% |
| Output Frequency | 50 Hz ± 0.2 Hz |
| Input Power Factor | >0.9 |
| Output Power Factor | 0.8 lag to Unity PF |
| Output Waveform | Pure Sine Wave |
| Technology |
IGBT-based PWM with Isolation Transformer |
| DC Voltage (Input) | 48V / 72V / 120V /192V DC |
| Overload Capacity |
150% for 1 minute; 125% for 10 minutes |
| Inverter Efficiency | 90% |
| Overall Efficiency | 85% |
| Crest Factor | 3:1 |
| Regulation | ±1% |
| Switching Frequency | Above 20 kHz |
| THD |
<3% for linear loads; <5% for non-linear loads |
| LCD Display |
Output voltage, current, frequency; Input voltage; Battery voltage
|
| Alarms |
On Battery, Low Battery, UPS Overload |
| Protections |
Auto discharge protection, overload, surge, input fault,
cold start, low battery, over-charge, output short circuit,
over temperature
|
| Load Test |
100% load on resistive load |